Test for Bacteria, Fungi, Mold to Monitor Biodiesel “Shelf Life”

One of the biggest advantages to using biodiesel fuels is that they can be used in existing engines and fuel injection systems with little or no affect on operating performance. However, by sheer composition, biodiesel fuels and biodiesel blends provide a natural food source for microbial growth. Testing can keep storage tanks free from bacteria.

According to the National Biodiesel Board, biodiesel fuels have an estimated “shelf life” of no more than six months. Along with using biocides to control biological growth, it also recommends efforts be made to control water contamination since aerobic fungus, bacteria and yeast hydrocarbon utilizing microorganisms (HUMBUGS) usually grow where the fuel and water meet.

Although biodiesel and biodiesel fuel blends aren't stored for long periods of time, water contamination is always a concern. And where there's water, there is great potential for microbial growth. Since biocides work where the HUMBUGS live - in the water - anaerobic colonies that can be active in sediments on tank surfaces may be unaffected by some biocide treatments and can cause extensive tank corrosion. POLARIS Laboratories® suggests testing for bacteria, fungi and mold every three months to be certain fuel in storage tanks is suitable for use.

Correction

Our article on lubricity in the August issue of the Condition Monitor incorrectly stated that the additional steps diesel fuels now undergo during the refining process reduce fuel lubricity. POLARIS Laboratories® acknowledges that these additional steps may, in some instances, reduce lubricity.

We feel it's important to clarify that not all ULSD fuel fails to meet the lubricity requirement as specified in ASTM D975-07a, the Standard Specification for Diesel Fuel Oils. Also, when using ASTM D6079 in the evaluation of fuel lubricity, the wear scar measurement should be <520µ (microns) to be considered to have sufficient lubricity to provide proper lubrication.

Print this Technical Bulletin (PDF - 90K)


Top

News

POLARIS Laboratories® Expands into Central America

POLARIS Laboratories® is again extending its global reach with a new laboratory in Guatemala City. The expansion supports the company's global strategy for continued growth and is indicative of the strength and potential of the Central American market.

Read More


POLARIS Laboratories® Makes Inc. 5000 List Third Year in a Row

For the third year in a row, POLARIS Laboratories® has been named to Inc. Magazine's List of 5000 Fastest Growing Privately-Held Companies in America.

Read More


Training

  • Nashville
    Cooling Systems Maintenance
    March 6, 2012

  • Nashville
    Oil Analysis
    March 7-8, 2012

  • Houston
    Cooling Systems Maintenance
    April 17, 2012

View complete schedule and registration information


Tradeshows & Conferences

  • UMA Motorcoach Expo
    Long Beach, CA
    February 8-12, 2012

  • PepsiCo Summit & Tradeshow
    San Antonio, TX
    February 13-16, 2012

View all tradeshows